Supercomputers/Sites/CINES
Montpellier · France
CINES
Operated by GENCI. Hosting 5 systems in this dataset, 3 of them currently operational.
- Systems hosted
- 5
- Installed Rmax
- 52.88 PFlop/s
- Recorded power
- 3.93 MW
- Cooling
- Direct liquid cooling, warm water
Facility facts
Power, cooling and efficiency figures for CINES, each with its own source and date.
| Fact | Value | As of | Basis | Source |
|---|---|---|---|---|
| PUE | 1.1 Figure quoted for the Adastra installation | 2021-11 | Operator stated | genci.fr |
| PUE | 1.1 CINES page on Occigen states PUE below 1.1 on the computing part, enabled by hot-water direct liquid cooling and adiabatic coolers; recorded as an upper bound of 1.1, scope limited to the compute system. | 2020-06 | Operator stated | cines.fr |
| Cooling | Occigen blades cooled by 35 C hot-water direct liquid cooling, with CINES-specific infrastructure using adiabatic coolers Page refers to the June 2020 TOP500 list; Occigen was later succeeded by Adastra. | 2020-06 | Operator stated | cines.fr |
| Heat reuse | Heat from the water circuit leaving the compute bays is recovered to heat all CINES buildings Described in CINES's Occigen page. | 2020-06 | Operator stated | cines.fr |
| Cooling | Machine room SM5, available since January 2014, was built for Occigen's hot-water cooling with dry coolers; Occigen's 2016 extension added 1 MW of capacity through new UPS and air-conditioning units From CINES's 45-year report (2024). | 2017 | Operator stated | cines.fr |
Systems at this site
| System | Rmax | Power | First operational | Status |
|---|---|---|---|---|
| Adastra 2 | 2.53 PFlop/s | 36.6 kW | 2024 | operational |
| Adastra | 46.10 PFlop/s | 921.48 kW | 2022 | operational |
| Occigen2 | 2.49 PFlop/s | 1.43 MW | 2017-01 | decommissioned |
| Occigen | 1.63 PFlop/s | 934.8 kW | 2014 | upgraded |
| Jade (CINES) | 128.40 TFlop/s | 608 kW | 2008 | decommissioned |
Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.