Supercomputers/Sites/NSC Data Centre, Linkoping

Linkoping · Sweden

NSC Data Centre, Linkoping

Operated by NSC. Hosting 6 systems in this dataset, 4 of them currently operational.

Systems hosted
6
Installed Rmax
9.91 PFlop/s
all eras, as reported
Recorded power
724 kW
where disclosed
Cooling
-

Facility facts

Power, cooling and efficiency figures for NSC Data Centre, Linkoping, each with its own source and date.

FactValueAs ofBasisSource
IT power 1 MW Karnhuset (built 2013) has a computer room capable of supporting 1 MW of IT equipment; the Hangaren hall (built 2009) is separate. Page undated. 2026 Operator stated nsc.liu.se
Power supplier Both data centres on 10 kV power distribution; district cooling supplied by Tekniska Verken Page undated, fetched 2026. 2026 Operator stated nsc.liu.se
Cooling District cooling: outdoor cooling towers make chilled water in winter, absorption chillers driven by district heating produce it in summer Hangaren has 500 kW air cooling plus a 500 kW water circuit added in 2009. 2026 Operator stated nsc.liu.se

Systems at this site

SystemRmaxPowerFirst operationalStatus
Berzelius 5.25 PFlop/s - 2021 operational
Tetralith 2.97 PFlop/s - 2018 decommissioned
Stratus (NSC) 910.00 TFlop/s - 2018 operational
Bifrost 326.47 TFlop/s 205 kW 2015 operational
Triolith 407.24 TFlop/s 519 kW 2012 decommissioned
Neolith 47.03 TFlop/s - 2007 operational

Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.