Supercomputers/Sites/NCAR Mesa Laboratory (Boulder)
Boulder, CO · USA
NCAR Mesa Laboratory (Boulder)
Operated by NCAR. Hosting 11 systems in this dataset, 0 of them currently operational.
- Systems hosted
- 11
- Installed Rmax
- 0.0 GFlop/s
- Recorded power
- 854.9 kW
- Cooling
- -
Facility facts
Power, cooling and efficiency figures for NCAR Mesa Laboratory (Boulder), each with its own source and date.
| Fact | Value | As of | Basis | Source |
|---|---|---|---|---|
| Facility power | 2 MW CISL slide at the ECMWF workshop of 2008-11-06 describes the Mesa Lab computing facility as a 2 MW facility, with 60 percent of power to computing and 40 percent to mechanical systems; historical. | 2008-11 | Operator stated | ecmwf.int |
| IT power | 1.2 MW 1.2 MW for computing, with UPS holding 1.2 MW for 15 minutes and two 1.5 MW diesel generators; historical 2008 slide. | 2008-11 | Operator stated | ecmwf.int |
| Cooling | Two 450-ton chillers feed water-cooled air handlers; two 1,500 gallon tanks store 44 F chilled water as a thermal buffer Historical 2008 slide; NCAR later moved its main supercomputing to the Wyoming centre. | 2008-11 | Operator stated | ecmwf.int |
| Cooling | For the Cray X-MP in 1986 the Mesa Laboratory computer room had its electrical power and grounding replaced and its cooling piping redesigned to add a backup chilled-water source | 1986-10 | Operator stated | cisl.ucar.edu |
Systems at this site
| System | Rmax | Power | First operational | Status |
|---|---|---|---|---|
| Antero 2 (NCAR C90) | - | 493.5 kW | 1997-01 | decommissioned |
| NCAR Cray T3D | - | 41.4 kW | 1994-07 | decommissioned |
| Graywolf (NCAR Cray-3) | - | 90 kW | 1993-10 | decommissioned |
| Littlebear (NCAR CM-5) | - | - | 1993-04 | decommissioned |
| Cray Y-MP | - | - | 1990-05 | decommissioned |
| CM-2 | - | - | 1988-09 | decommissioned |
| Cray X-MP | - | - | 1986-10 | decommissioned |
| NCAR Cray-1A S/N 14 | - | 115 kW | 1983-05 | decommissioned |
| NCAR Cray-1A S/N 3 | - | 115 kW | 1977-07 | decommissioned |
| NCAR CDC 7600 | - | - | 1971-05 | decommissioned |
| NCAR CDC 6600 | - | - | 1965-12 | decommissioned |
Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.