COMPUTE ATLAS Supercomputer supply-chain graph
1581 systems 558 sites Sourced data

Supercomputers/Sites/MPCDF Garching

Garching · Germany

MPCDF Garching

Operated by MPCDF. Hosting 9 systems in this dataset, 4 of them currently operational.

Systems hosted
9
Installed Rmax
57.83 PFlop/s
all eras, as reported
Recorded power
5.69 MW
where disclosed
Cooling
-

Facility facts

Power, cooling and efficiency figures for MPCDF Garching, each with its own source and date.

FactValueAs ofBasisSource
Facility power 4.7 MW Average total power supply of the production supercomputers as of September 2024 (infrastructure 15 percent, compute including storage 85 percent); the largest of the eight German centres surveyed. 2024-09 Operator stated arxiv.org
Cooling Direct liquid cooling since the 2008 Cray-era experience, four clusters of 300 to 1000 kW at 16 to 40 C inlet, plus 3 MW of spring-water cooling (14 C to 20 C maximum) German HPC centres energy-aware operation survey, Table 2. 2024-09 Operator stated arxiv.org
Heat reuse No heat reuse in operation; plans from 2030 for up to 70 percent heat reuse on campus and possibly a city district network Table 3 of the survey; the plan is a future intention. 2024-09 Operator stated arxiv.org

Systems at this site

SystemRmaxPowerFirst operationalStatus
Viper-GPU 31.10 PFlop/s 499.98 kW 2025-02 operational
Viper-CPU 4.29 PFlop/s 784 kW 2024-06 operational
Raven-GPU 8.62 PFlop/s 377 kW 2021-06 operational
COBRA 5.61 PFlop/s 1.64 MW 2018 decommissioned
Draco 790.70 TFlop/s - 2016-05 decommissioned
Hydra (MPCDF) 1.28 PFlop/s 1.26 MW 2013-10 decommissioned
VIP (Garching) 80.32 TFlop/s 1.07 MW 2008 decommissioned
Genius (Garching) 21.91 TFlop/s 63 kW 2007-10 decommissioned
DAIS 6.03 PFlop/s - - operational

Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.