Supercomputers/Sites/Eni Green Data Center
Ferrera Erbognone · Italy
Eni Green Data Center
Operated by Eni. Hosting 5 systems in this dataset, 5 of them currently operational.
- Systems hosted
- 5
- Installed Rmax
- 1.10 EFlop/s
- Recorded power
- 22.00 MW
- Cooling
- Direct liquid cooling, warm water
Facility facts
Power, cooling and efficiency figures for Eni Green Data Center, each with its own source and date.
| Fact | Value | As of | Basis | Source |
|---|---|---|---|---|
| Machine-room floor area | 5,200 m2 Riello UPS case study: 5,200 m2 of computer systems area in six IT rooms (2,600 m2 in phase 1); building area 45,000 m2. Siemens reference gives about 5,400 m2. Both undated; centre opened 2013. | 2013 | Vendor stated | riello-ups.comassets.new.siemens.com |
| Facility power | 30 MW Final UPS electrical power 30 MW (phase 1 was 7.2 MW); Siemens estimates consumption of 30 MW with peaks to 36 MW. Pre-HPC6 figures. | 2013 | Vendor stated | riello-ups.comassets.new.siemens.com |
| Cooling | Primary cooling by direct outside-air free cooling Riello UPS case study of the Green Data Center; HPC6 later added liquid cooling for the machine itself. | 2013 | Vendor stated | riello-ups.com |
| PUE | 1.2 Both vendors state an annual PUE below 1.2 (an upper bound, recorded as 1.2); design or commissioning claim, not a measured figure for HPC6 era. | 2013 | Vendor stated | riello-ups.comassets.new.siemens.com |
Systems at this site
| System | Rmax | Power | First operational | Status |
|---|---|---|---|---|
| HPC7 | 571.5 PFlop/s | 8.73 MW | 2026-06 | operational |
| HPC6 | 477.9 PFlop/s | 8.46 MW | 2024-11 | operational |
| HPC5 | 35.45 PFlop/s | 2.25 MW | 2020 | operational |
| HPC4 | 12.21 PFlop/s | 1.32 MW | 2018-01 | operational |
| HPC2 | 3.19 PFlop/s | 1.23 MW | 2014 | operational |
Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.