Supercomputers/Sites/ABCI Data Center, Kashiwa
Kashiwa · Japan
ABCI Data Center, Kashiwa
Operated by AIST. Hosting 4 systems in this dataset, 3 of them currently operational.
- Systems hosted
- 4
- Installed Rmax
- 261.8 PFlop/s
- Recorded power
- 8.68 MW
- Cooling
- Direct liquid cooling, warm water
Facility facts
Power, cooling and efficiency figures for ABCI Data Center, Kashiwa, each with its own source and date.
| Fact | Value | As of | Basis | Source |
|---|---|---|---|---|
| PUE | 1.1 Reported as below 1.1; sites.csv already holds 1.1 | 2025-01 | Press report | monoist.itmedia.co.jp |
| Cooling | Fan coil units stacked on top of racks handle hot-aisle heat; 5.2 MW cooling capacity | 2025-01 | Press report | monoist.itmedia.co.jparxiv.org |
| Facility power | 5.2 MW ABCI page (information as of December 2024): AI data center building power capacity 5.2 MW, matching its cooling capacity. | 2024-12 | Operator stated | abci.ai |
| Cooling | Free cooling using only cooling towers (10 towers, 5 MW, up to 9,000 l/min) plus a 200 kW chiller; cooling pods give 70 kW per rack Total cooling capacity above 5.2 MW; four pods holding 144 racks at the time of the page. | 2024-12 | Operator stated | abci.ai |
| Machine-room floor area | 455 m2 Server room stated as 62 ft x 79 ft (about a basketball court), ceiling height 20 ft; area computed from those dimensions. | 2024-12 | Operator stated | abci.ai |
| Facility power | 6 MW Electrical capacity of the ABCI hall after the ABCI 3.0 upgrade; 5.2 MW cooling capacity and 144 racks | 2024-11 | Operator stated | arxiv.org |
Systems at this site
| System | Rmax | Power | First operational | Status |
|---|---|---|---|---|
| ABCI 3.0 | 145.1 PFlop/s | 3.60 MW | 2025-06 | operational |
| ABCI-Q | 74.58 PFlop/s | 1.83 MW | 2025-06 | operational |
| ABCI 2.0 | 22.21 PFlop/s | 1.60 MW | 2021 | operational |
| ABCI | 19.88 PFlop/s | 1.65 MW | 2018-08 | decommissioned |
Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.