Supercomputers/Sites/TU Wien Science Center Data Center
Vienna · Austria
TU Wien Science Center Data Center
Operated by Austrian Scientific Computing. Hosting 1 system in this dataset, 0 of them currently operational.
- Systems hosted
- 1
- Installed Rmax
- 0.0 GFlop/s
- Recorded power
- 0 kW
- Cooling
- -
Facility facts
Power, cooling and efficiency figures for TU Wien Science Center Data Center, each with its own source and date.
| Fact | Value | As of | Basis | Source |
|---|---|---|---|---|
| IT power | 2 MW Up to 2 MW made available for the complete AI:AT system, plus a UPS of up to 100 kW for storage, network and administrative servers | 2026-03-27 | Operator stated | ec.europa.eu |
| Cooling | Two water loops: a primary hot-water loop to rooftop free-cooling units with inlet up to 40 C, sized at 2 MW to remove at least 90 percent of direct water-cooled heat, and an 18 C loop for air-cooled equipment EuroHPC AI:AT tender; the server room has a raised floor and summer outside air of about 35 C with peaks of 38 to 40 C | 2026-03-27 | Operator stated | ec.europa.eu |
Systems at this site
| System | Rmax | Power | First operational | Status |
|---|---|---|---|---|
| AI:AT | - | - | - | planned |
Facility fields are recorded only where a public source states them. Blank means we have not found one, not that the value is zero: an important distinction if you are aggregating power or PUE across sites.