SciNet (University of Toronto)

Operated by SciNet. Hosting 4 systems in this dataset, 2 of them currently operational.

Systems hosted
4
Installed Rmax
13.81 PFlop/s
all eras, as reported
Recorded power
1.25 MW
where disclosed
Cooling
-

Facility facts

Power, cooling and efficiency figures for SciNet (University of Toronto), each with its own source and date.

FactValueAs ofBasisSource
PUE 1.2 SciNet paper (J. Phys. Conf. Ser. 256, 2010): measured average annual PUE below 1.2 (recorded as an upper bound), design point 1.16. Describes the original GPC/TCS data centre. 2010 Operator stated pages.scinet.utoronto.ca
Machine-room floor area 290 m2 Computer room of 3,100 sq ft (290 m2) within 12,000 sq ft of rented warehouse space roughly 30 km north of the St. George campus. 2010 Operator stated pages.scinet.utoronto.ca
Facility power 4 MW Local power availability of about 4 MW through a dedicated, separately metered 600 V, 4,000 A feed; the systems themselves approached 2 MW. 2010 Operator stated pages.scinet.utoronto.ca
Cooling Direct-to-rack water cooling with a centrifugal chiller and rooftop cooling tower; three 35-ton air handlers for the remaining air-cooled row Same 2010 paper; original facility design. 2010 Operator stated pages.scinet.utoronto.ca

Systems at this site

SystemRmaxPowerFirst operationalStatus
Trillium 9.49 PFlop/s - 2025-08-07 operational
Niagara 3.60 PFlop/s 919.42 kW 2018-03 decommissioned
BGQ (SOSCIP) 715.55 TFlop/s 328.75 kW 2012-08 decommissioned
Killarney - - - operational